| Manufacture | HIMA |
| Item No | F3330 |
| Article number | F3330 |
| Series | PLC Module |
| Origin | United States(US) |
| Dimension | 85*11*110(mm) |
| Weight | 0.8 kg |
| Customs Tariff Number | 85389091 |
| Type | Output Module |
HIMA F3330 The module is automatically tested during operation. The main test routines are: – Reading back of the output signals. The operating point of the 0 signal read back is ≤ 6.5 V. Up to this value the level of the 0 signal may arise in case of a fault and this will not be detected – Switching capability of test signal and cross-talking (walking-bit test). Outputs 500 mA, k short circuit proof Internal voltage drop max. 2 V at 500 mA load Admissible line resistance (in + out) max. 11 Ohm Undervoltage tripping at ≤ 16 V Operating point for short circuit current 0.75 ... 1.5 A Outp. leakage current max. 350 µA Output voltage if output is reset max. 1,5 V Duration of the test signal max. 200 µs Space requirement 4 TE Operating data 5 V DC: 110 mA,24 V DC: 180 mA in add. load