| Manufacture | ABB |
| Item No | AI835 |
| Article number | 3BSE051306R1 |
| Series | 800XA Control Systems |
| Origin | Sweden |
| Dimension | 102*51*127(mm) |
| Weight | 0.2 kg |
| Customs Tariff Number | 85389091 |
| Type | Analog Input Module |
Detailed data: Resolution 15 bits Input impedance > 1 MΩ Isolation Group to ground Error 0.1% max Temperature drift 5 ppm/°C typical, 7 ppm/°C max Update period 280 + 80 * (number of active channels) ms at 50 Hz; 250 + 70 * (number of active channels) ms at 60 Hz Maximum field cable length 600 m (656 yards) CMRR, 50Hz, 60Hz 120 dB NMRR, 50Hz, 60Hz > 60 dB Rated insulation voltage 50 V Dielectric test voltage 500 V AC Power dissipation 1.6 W Current consumption +5 V module bus 75 mA Current consumption +24 V module bus 50 mA Current consumption +24 V external 0Frequently asked questions about the product are as follows: -What is ABB AI835 3BSE051306R1? ABB AI835 3BSE051306R1 is an analog input module in ABB Advant 800xA system, mainly used for thermocouple/mV measurement. -What are the aliases or alternative models of this module? Aliases include AI835A, and alternative models include U3BSE051306R1, REF3BSE051306R1, REP3BSE051306R1, EXC3BSE051306R1, 3BSE051306R1EBP, etc. What is the special function of channel 8? Channel 8 can be configured as a "cold junction" (ambient) temperature measurement channel, as a cold junction compensation channel for channels 1-7, and its junction temperature can be measured locally on the screw terminals of the MTU or on a connection unit away from the device.