| Manufacture | ABB |
| Item No | AI830 |
| Article number | 3BSE008518R1 |
| Series | 800XA Control Systems |
| Origin | Sweden |
| Dimension | 102*51*127(mm) |
| Weight | 0.2 kg |
| Customs Tariff Number | 85389091 |
| Type | Input Module |
Detailed data: Error Error depends on field cable resistance: Rerr = R* (0.005 + ∆R/100) Terr°C = Rerr / (R0 * TCR) Terr°F = Terr°C * 1.8 Update period 150 + 95 * (number of active channels) ms CMRR, 50Hz, 60Hz >120 dB (10Ω load) NMRR, 50Hz, 60Hz >60 dB Rated insulation voltage 50 V Dielectric test voltage 500 V AC Power consumption 1.6 W Current consumption +5 V Modulebus 70 mA Current consumption +24 V Modulebus 50 mA Current consumption +24 V external 0Frequently asked questions about the product are as follows: -What is ABB AI835 3BSE051306R1? ABB AI835 3BSE051306R1 is an analog input module in ABB Advant 800xA system, mainly used for thermocouple/mV measurement. -What are the aliases or alternative models of this module? Aliases include AI835A, and alternative models include U3BSE051306R1, REF3BSE051306R1, REP3BSE051306R1, EXC3BSE051306R1, 3BSE051306R1EBP, etc. What is the special function of channel 8? Channel 8 can be configured as a "cold junction" (ambient) temperature measurement channel, as a cold junction compensation channel for channels 1-7, and its junction temperature can be measured locally on the screw terminals of the MTU or on a connection unit away from the device.